Temperature sensors

Pt 1000 ohm / 0°C

AKS 11, AKS 12, AKS 21

Application

These sensors are recommended for accurate temperature meas-urement in applications such as superheating, food safety logs, and other important temperature measurement applications.Functional description

The sensor unit consists of a platinum element the resistance value of which changes proportionally with the temperature. Pt 1000 ohm sensor (1000 ohm at 0°C).

The sensors are adjusted and meet the tolerance requirements of EN 60751 Class B.

Temperature

Sensor/

range

sensor body

°C

Connection/cable

Enclo-sure

Time con-stant [s]

Cable length m3.5 m

Surface and duct sensor

Top: PPO (Noryl) Bottom: stainless steel

PVC cable, 2 x 0.2 mm2

3 1)10 2)35 3)

3.5 m + AMP5.5 m5.5 m + AMP8.5 m8.5 m + AMP1.5 m

AKS 12

Air temperature sensor

-40 to 80

18/8 stainless steel

PVC cable 2 x 0.22 mm2

IP 67

15 1)

3.5 m5.5 m5.5 m + AMP 13.5 m

Surface sensor with clip

Surface sensor with shielded cable and clip

Multipurpose sensor

-70 to +180

18/8 stainless steel

Fire-resistant silicone

rubber cable, 2 x 0.2 mm2

IP 67

6 1) 14 2) 35 3)

2.5 m5.0 m2.0 m2.5 m

Immersion sensor, 18/8 stainless steel tube

-70 to +180

Weld nipple: free cutting steelThread nipple: free cutting steel

TypeDescriptionQty1110170150130303030201111

Code084N0003084N0050084N0005084N0051084N0008084N0052084N0036084N0035084N0039084N0038084N0037084N0034084N2007084N2008084N2024084N2003

AKS 11 *)-50 to +100IP 67

AKS 21A **)

-70 to +180-70 to +180

AKS 21M

AKS 21W

Immersion sensor with cable and senor pocket, welded versionFire-resistant silicone rub-ber cable, 2 x 0.2 mm2

IP 5618 1)2.5 m1084N2017

*)

**)

Recommended for measuring superheat Recommended for hot gas systems

) Agitated liquid. ) Clamped to pipe. 3

) Air 4 m/s.

12

194 RK0YG402 © Danfoss 12/2009 AKS 11, 12, 21

AKS 11, AKS 12, AKS 21

°C 01 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1718 19 20 21 2223 24 25 2627 28 2930 3132 3334 35 36 37 38 39 40 41 424344 45 47 48 4950

ohm 1000.01003.91007.81011.71015.61019.5 1023.41027.31031.21035.11039.0 1042.91046.81050.71054.61058.5 1062.41066.3 1070.21074.01077.91081.81085.7 10.61093.51097.3 1101.21105.11109.01112.81167.7 1120.61124.51128.3 1132.21136.1 1139.91143.81147.71151.51155.4 1159.3 1163.1 1167.0 1170.8 1174.7 1178.51182.4 1186.3 1190.11194.0

°C −1−2−3−4−5−6−7 −8−9−10 −11−12−13 −14−15 −16−17−18−19−20 −21−22−23−24−25 −26−27−28−29 −30 −31−32−33−34−35 −36−37−38−39−40 −41−42−43 −44−45 −46 −47 −48 −49 −50

ohm 1000.0 996.1992.2988.3984.4 980.4 976.5 972.6968.79.60.9 956.9953.0949.1945.2941.2 937.3933.4929.5925.5921.6 917.7913.7909.05.9901.9 8.0 4.00.1886.2882.2 878.3 874.3870.4866.4862.5 858.5854.6850.6 846.7842.7 838.8 835.0 830.8 826.9 822.9 818.9 815.0 811.0 807.0 803.1

approx. 3.9 ohm/K

AKS 11

AKS 12

AKS 21A, AKS 21M

AKS 21W

AKS 21W

welded version

Pocket in welded version for AKS 21W

The tolerance of a Pt1000 sensor is less than ±(0.3 + 0.005 T).

This translates into a temperature error of less than 0.5 degree for refrigeration control.

Sensors with AMP plug:

connector type AMP ital mod 2, housing 280 358,crimp contacts type 280 708-2AKS 11, 12, 21

RK0YG402 © Danfoss 12/2009